HONEYWELL FC-PSU-UNI2450U V2.1機器人模塊, FC-PSU-UNI2450U V2.1說(shuō)明書(shū)文檔
某些總線(xiàn)狀況可能會(huì )影響網(wǎng)絡(luò )輸入/輸出
事件,如冗余總線(xiàn)的同時(shí)切換、部分總線(xiàn)斷開(kāi)(其中一個(gè)
雙絞線(xiàn))或其他總線(xiàn)在潛在仲裁器上斷開(kāi)可能會(huì )導致網(wǎng)絡(luò )。

無(wú)法通過(guò)TCP/IP存儲硬件配置
無(wú)法通過(guò)FIP TCP/IP成功存儲硬件配置
FC-PSU-UNI2450U V2.1
未設置通用輸入數據的點(diǎn)故障觸點(diǎn)
當無(wú)法成功使用通用設備的COMV時(shí),點(diǎn)故障
未設置通用輸入數據的聯(lián)系人。他們總是很清楚。但是,如果
生成通用數據的設備丟失,用戶(hù)故障觸點(diǎn)設置正確。
Ping 3000字節或更多的消息可能會(huì )導致FBC掛起
如果向FBC發(fā)送3000字節或更多的Ping消息,可能會(huì )導致掛起或
HONEYWELL FC-PSU-UNI2450U V2.1機器人模塊
使FBC模塊崩潰。
Certain Bus Conditions May Affect Network I/O
Events such as simultaneous switching of redundant busses, partial bus breaks (one of
twisted pair), or a different bus broken on potential arbiters may cause glitches of I/O on
the network.
Hardware Configuration Cannot Be Stored via TCP/IP
The hardware configuration cannot be successfully stored through a FIP TCP/IP
connection.
Point Fault Contacts For Generic Input Data Are Not Set
When a COMV from a generic device cannot be consumed successfully, the point fault
contacts for the generic input data are not set. They are always clear. However, if the
device that produces the generic data is lost, the subscriber fault contact is correctly set.
Ping Messages of 3000 Bytes or More May Cause the FBC to Hang
If a Ping message of 3000 bytes or more is sent to the FBC, it may result in hanging or
crashing the FBC module.