主營(yíng)產(chǎn)品
PLC可編程控制器模塊,DCS卡件,ESD系統卡件,振動(dòng)監測系統卡件,汽輪機控制系統模塊,燃氣發(fā)電機備件等,優(yōu)勢品牌:Allen Bradley、BentlyNevada、ABB、Emerson Ovation、Honeywell DCS、Rockwell ICS Triplex、FOXBORO、Schneider PLC、GE Fanuc、Motorola、HIMA、TRICONEX、Prosoft等各種進(jìn)口工業(yè)零部件
產(chǎn)品廣泛應用于冶金、石油天然氣、玻璃制造業(yè)、鋁業(yè)、石油化工、煤礦、造紙印刷、紡織印染、機械、電子制造、汽車(chē)制造、塑膠機械、電力、水利、水處理/環(huán)保、鍋爐供暖、能源、輸配電等等
INDEL AG INFO-4KP-94161數字量模塊
延遲/積分器(延遲)A、 應用通用定時(shí)器
對脈動(dòng)二進(jìn)制信號進(jìn)行積分,以獲得連續信號,例如失磁功能輸出(失步保護)或反向功率保護
短I/P信號的延長(cháng)(脈沖延長(cháng))簡(jiǎn)單時(shí)間延遲。
B、 特征可分配給的二進(jìn)制I/P信道二進(jìn)制I/P信號2保護功能跳閘信號(跳閘)所有I/P通道都可以反轉。
可調復位時(shí)間2延時(shí)類(lèi)型積分:僅I/P信號處于邏輯“1”在延時(shí)結束時(shí)計數。
無(wú)積分:從定時(shí)器瞬間開(kāi)始的總時(shí)間開(kāi)始,直到重置或到期計數。
啟用和禁用各種功能可以啟用和禁用該功能的許多功能。
t1激活此設置提供了禁用計時(shí)器t1的功能。當禁用時(shí),不會(huì )生成“重復跳閘”組信號。
t2激活此設置提供了禁用定時(shí)器t2的功能。當禁用時(shí),不會(huì )生成任何“備用跳閘”組信號。
重新激活該設置提供了禁用傳輸跳閘的設施。
什么時(shí)候如果禁用,則不會(huì )生成任何“遠程跳閘”組信號。EFP活動(dòng)此設置提供了禁用端故障保護的功能。
禁用時(shí),“結束故障”信號組中沒(méi)有一個(gè)生成。
紅色活性
該設置為禁用冗余保護提供了便利。禁用時(shí),不會(huì )生成任何“冗余”信號組。開(kāi)始下一幕。
該設置提供了禁用無(wú)條件跳閘的設施特色禁用時(shí),“無(wú)條件跳閘”
生成一組信號。跳閘延遲輸入端的啟動(dòng)信號和跳閘信號之間的時(shí)間在輸出端。
復位延遲輸入信號出現后計時(shí)器復位所需的時(shí)間消失。
整合存在時(shí)函數響應的確定
脈動(dòng)I/P信號:0:延遲繼續運行,前提是I/P信號不會(huì )消失超過(guò)重置時(shí)間。
1: 積分I/P處于邏輯“1”的時(shí)間,即,在邏輯“1“時(shí)間之和等于設定延遲時(shí)間之前,不會(huì )發(fā)生跳閘。
Delay/integrator (Delay)
A. Application
General purpose timer for
integration of pulsating binary signals to obtain a continuous
signal, e.g. output of the loss-of-excitation function (out-ofstep protection) or reverse power protection
extension of short I/P signals (pulse prolongation)
simple time delay.
B. Features
binary I/P channel assignable to
binary I/P signals
2 protection function tripping signals (trips)
All I/P channels can be inverted.
adjustable reset time
2 types of time delay
Integration: Only the time during which the I/P signal is at
logical "1" counts at the end of the time delay.
No integration: The total time from the instant the timer
starts until it is either reset or expires counts.
Enabling and disabling the various features
A number of the function’s features can be enabled and disabled.
t1 active
This setting provides facility for disabling the timer t1. When it is
disabled, none of the “repeat trip” group of signals is generated.
t2 active
This setting provides facility for disabling the timer t2. When it is
disabled, none of the “backup trip” group of signals is generated.
RemTrip active
This setting provides facility for disabling transfer tripping. When
it is disabled, none of the “remote trip” group of signals is generated.
EFP active
This setting provides facility for disabling the end fault protection.
When it is disabled, none of the “end fault” group of signals is
generated.
Red active
This setting provides facility for disabling the redundant protection. When it is disabled, none of the “redundant” group of signals is generated.
Start Ext act.
This setting provides facility for disabling the unconditional trip
feature. When it is disabled, none of the “unconditional trip”
group of signals is generated.Trip-Delay
Time between start signal at the input and the tripping signal
at the output.
Reset-Delay
Time required for the timer to reset after the input signal has
disappeared.
Integration
Determination of the response of the function in the presence
of a pulsating I/P signal:
0: The delay continues to run, providing the I/P signal does
not disappear for longer than the reset time.
1: The time during which the I/P is at logical "1" is integrated, i.e. tripping does not take place until the sum of logical "1" time equals the set delay time.